Cleanrooms provide the following features:

Clean Rooms

SPECIFICATIONS:

Panel General - Panels are to be 3" thick and fully fabricated. Heights over 8' may use horizontal H-mull depending on substrate limitations.

Panel Substrate #1 - 1/8" regular hardboard, Physical properties - tensile strength angled at surface 4900 PSI, perpendicular to surface 215 PSI, modulus rupture 8400 PSI.

Panel Substrate #2 - 1/2" Gypsum, 3/4" Hour fire rated.

Panel Substrate #3 - 5/8" Type "X" Gypsum, 1 Hour fire rated.

Panel Surfaces- White Vinyl, thickness 4 mil, flame resistant class "A", no maintenance. Optional choices include: Steel, Vinyl, HPL, FRP, PVC, Porcelain, Stainless steel, Kydex, Aluminum …

Panel Core #1 - Expanded Polystyrene, 1 pound density, fire retardant class "A", flame spread 15, Smoke development 25-85, insulation R-12, U-.09, effective temperature range 180 degrees Fahrenheit, water absorption less than 2%, approved material Southern Building Code Congress. Factory Mutual Approved.

Panel Post System - Super Structure Post System, 20 gauge painted white with a matching snap in feature filler to conceal the fasteners. Posts are a major structural element capable of supporting 2000 pounds, they are also used to house structural inserts capable of supporting 12,000 pounds. Posts are used to conceal all electrical wiring, telephone wiring and computer cabling. The two-piece design allows for a non-progressive panel system, which means panels can be removed and replaced without disturbing adjacent panels. All panels of like size are interchangeable.

New - Clean Room Class 10 System, non-progressive aluminum system, powder coated white finish. Flush design and clamps down on panel for sealing. Design eliminates the need for feature strips.

New - Clean-line system. Requires no post, panels butt together giving one clean sealable seam. Available in metal surfaces only.

Base Channel - Base Channels shall be a continuos, substantial steel "U" channel finished to match the post system. When fastened to floor shall securely support the wall panels and not require additional pieces such as cove molding for a finished appearance.

Doors and Frames - Heavy duty steel doors shall be 1-3/4" thick, 3' x 7'. Doors are to be sealed with a fully gasketed jamb. Doors shall be finished to match the walls. All doors shall include thresholds and stainless steel lock sets. Doors shall be pre-hung at factory to insure proper fit. Doors are expected to be field adjusted and leveled to insure proper operation.

Hardware - Hardware shall be commercial grade the standard of National Partitions, unless otherwise specified. Doors will be outfitted with key, lock and one and one half pair 4-1/2" butt hinges.

Steel Roof Panel Option #1 - 26 gauge Steel faced panelized roof with polystyrene core 3" or 4" thick depending on span.

Steel Roof Decking Option #2 - Corrugated 22 gauge steel, fire rating noncombustible, sound deadening with closure gaskets STC 32.

Ceiling Grid and tile - Heavy duty grid with vinyl faced metal ceiling tile is available.

Electrical option #1- Modular wiring quick connect system, UL listed components, conforms to National Electric Code, connects all outlets, lights and switches and terminates with a 6 wire "pig-tail" at designated location, final hook up to distribution panel and power to the building is not included and should be provided by a licensed electrician. Special sealed lights should be provided by a local contractor (modular wiring pigtails are available for this). Outlets are convenience type duplex, three wire, grounded. Switches are quiet type.

Electrical option #2- Standard package includes: UL listed components and conforms to National Electric Code. Outlets and switches have junction boxes, EMT conduit, couplings and 90 degree elbows that extend into the plenum area. All wiring and light conduit is not included. A licensed electrician is required to complete the wiring. Sealed lights should be provided locally. Outlets are convenience type duplex, three wire, grounded. Switches are quiet type.

Glass - Glazed panels will be picture window type and unless otherwise specified, be sized to full 40" in height, by full panel width. Design shall be beveled sills on the frame, height shall be 41" from the floor. All glass shall be 3/16" tempered safety type and assembled in frame. Glazed panels are to be shipped in three sections. Optional glass: 1/4" laminated, insulated, wire, tinted, polycarbonate etc.

DEFINITIONS:

Air Showers - Chambers located between the clean room and an outside environment that remove particulate contamination from cleanroom garments as personnel pass through. The chambers may include HEPA filters, interlocking doors, a recirculating air system, and air nozzles in various patterns through which filtered air is blown onto the personnel in the shower. The air is moved over the worker, removing particulate contamination from the worker's garments.

Airborne Particulate Cleanliness Classes - The Statistically allowable number of particles per cubic foot of air according to federal standard 209E.

Measured particle size in micrometers (M)

Class Name

0.1 M

0.2 M

0.3 M

0.5 M

5 M

1 (M 1.5)

35

7.5

3

1

N/A

10 (M 2.5)

350

75

30

10

N/A

100 (M 3.5)

N/A

750

300

100

N/A

1000 (M 4.5)

N/A

N/A

N/A

1,000

7

10000 (M 5.5)

N/A

N/A

N/A

10,000

70

100000 (M 6.5)

N/A

N/A

N/A

100,000

700

Ceiling Grid Systems - Frameworks of parallel and perpendicular bars used to house filters and light fixtures in cleanroom ceilings. The grids may include a gel or other type of sealant for providing an air tight seal around the filters.

Cleanroom - A room in which the concentration of airborne particles is controlled to specified limits. (Federal Standard 209E)

Federal Standard 209E - The document that establishes standard classes of air cleanliness for airborne particulate levels in cleanrooms and clean zones. it prescribes methods for class verification and monitoring of air verification and monitoring air cleanliness. It also addresses certain other factors, but only as the affect control of airborne particulate contamination.

Filter Modules - Units that house a HEPA or ULPA filter. The units are mounted into cleanroom ceilings, walls or benches and provide filtered air flow.

Flooring - Various types of flooring are used in cleanrooms, depending upon cleanliness levels. Contamination control flooring may have a tacky finish to trap dust and other debris from wheels and shoes. Access flooring consists of solid or perforated panels or raised pedestals. Air can flow through perforated panels and can be exhausted in a subfloor area. Vinyl flooring features sealed seams to prevent accumulation of contamination. Static Dissipative flooring prevents static buildup and electrostatic discharge.

HEPA Filters - High efficiency particulate air filters are replaceable extended-media dry-type filters in a rigid frame having a minimum particle collective efficiency of 99.97 percent for a 0.3 micron particle, and a maximum clean filter pressure drop of 2.54 cm (1") water gauge when tested at rated airflow capacity.

Laminar Flow - Airflow in which essentially the entire body of air within a confined area moves with uniform velocity and direction as the ambient atmosphere being sampled.

Lighting - Room lighting is supplied by ceiling mounted modules, often incorporated into ceiling HEPA filter modules. Work area lighting may be supplied by illuminators (concentrated light sources that are placed next to the work area which can be adjusted to focus light on a desired area. Fixtures are sealed to prevent contamination.

Particle - A solid or liquid object, generally between .001 micron and 1000 microns in size.

Particulate - A substance that consists of particles (minute quantities of solid or liquid matter).

Pass-Throughs or Pass-Thrus - Openings in walls with two doors through which materials and objects are passed. Pass-Through doors interlock so that one door always is closed while the other is open.

Prefilters - Replaceable filters installed before a final filter to remove gross contaminants and protect the final filter from environmental conditions. The prefilters have a lower efficiency than the one they protect.

Sealants - Used to seal HEPA filters into ceiling grid systems. Plastic, silicone and gel sealants are commonly used.

Testing/Certification Services - Independent, contract services for the testing and certification of HEPA filters, laminar flow equipment, safety cabinets and HVAC systems. Certification and testing of HEPA filters includes leak testing, scanning, electrical testing, particle count surveys, sound level measurement, vibration measurement, temperature and humidity measurement, airflow balancing, gas system testing, light level measurement and room pressurization. Product qualification testing and environmental analysis/testing also are available.

Turnkey - A method of construction, design, installation, etc. Assumes total responsibility from design through completion of the project.

ULPA Filter - Ultra low penetration air filters are extended media dry filters in a rigid frame that have a minimum particle collection efficiency of 99.999 percent for particles greater than or equal to .12 micron in size.

CLEANROOM DESIGN CRITERIA

Criteria

Class 10

Class 100

Class 1000

Class 10000

Class 100000

Minimum wall surface Steel - porcelain or epoxy paint High pressured laminate or SmoothSteel Vinyl Vinyl Vinyl
Optional surface Steel - porcelain or epoxy paint Smooth steel, HPL Embossed Steel Embossed Steel
Paints Epoxy Epoxy, Powder, Enamel Epoxy, Powder, Enamel Latex, Enamel Latex, Enamel
NPI window type Beveled Sill Beveled Sill Beveled Sill Beveled Sill Beveled Sill
Lights Incorporated in HEPA filter Incorporated in HEPA filter Special sealed

fixture

Special sealed fixture Special sealed fixture
Air change/hour 600 250-600 150-250 75-120 10-30
Filter cover 100% 70-100% 30-60% 10-30% 5-10%
Filter velocity 70-110 FPM 70-110 FPM 70-110 FPM 70-110 FPM 70-110 FPM
Filter type 99.999 (5-9's) 99.99 (4-9's) 99.99 (4-9's) 99.97 minimum 99.97 minimum
Ceiling design Mod/T bar Mod/T bar T-bar T-bar T-bar
Grid gasketed gasketed gasketed gasketed gasketed
Grid support special item All-thread w/ unistrut all-thread rod turnbuckles All-thread w/ unistrut all-thread rod turnbuckles 12 ga wire to grid. 10 ga wire to filter turnbuckles at filter 12 ga wire to grid. 10 ga wire to filter turnbuckles at filter 12 ga wire to grid. 10 ga wire to filter turnbuckles at filter
Ceiling panel Capaul Enviroguard 1180 or Mylar E or Conwed Clean Room
Special items Hold down clips Hold down clips Hold down clips Hold down clips optional hold down clips
Flooring (depends on room use) Mipolam or Equal Mipolam or equal Mipolam or equal Sheet vinyl Sheet vinyl
Base Molding 6" Cove 6" Cove 6" Cove 6" Cove 4" Rubber
Optional Floor

Conductive or non conductive HPL

Perforated access Perforated access Perforated access Optional Optional
Certification Filter and room scan/report Filter and room scan/report Filter and room scan/report Filter and room scan/report Filter and room scan/report

 

Request for Quote / Information Click